Package: org.gridsuite.modification
Interface to decouple filter evaluation and remote filter service resolution from the core modification engine.
public interface IFilterService {
/**
* Fetches filter definitions by their UUIDs.
*
* @param filtersUuids list of filter UUIDs
* @return list of AbstractFilter objects
*/
List<AbstractFilter> getFilters(List<UUID> filtersUuids);
/**
* Resolves filters against a live network and streams matching equipment.
*
* @param filtersUuids list of filter UUIDs
* @param network the network to resolve against
* @return stream of matched equipment per filter
*/
Stream<org.gridsuite.filter.identifierlistfilter.FilterEquipments> exportFilters(
List<UUID> filtersUuids, Network network);
/**
* Returns a map from filter UUID to the equipment matched by that filter.
*
* @param network the network to resolve against
* @param filters map of filter UUID → filter name
* @return map of filter UUID → FilterEquipments
*/
Map<UUID, FilterEquipments> getUuidFilterEquipmentsMap(Network network, Map<UUID, String> filters);
}Package: org.gridsuite.modification
Interface for retrieving stored load-flow parameters by UUID for modifications that execute power flow simulations.
public interface ILoadFlowService {
/**
* Retrieves load-flow parameters by UUID.
*
* @param loadFlowParametersUuid the UUID of the stored parameters
* @return LoadFlowParametersInfos populated with all load-flow settings
*/
LoadFlowParametersInfos getLoadFlowParametersInfos(UUID loadFlowParametersUuid);
}Package: org.gridsuite.modification.modifications
Extends: com.powsybl.iidm.modification.AbstractNetworkModification
The abstract base class for all concrete modification implementations.
| Method | Description |
|---|---|
void check(Network network) |
Validates inputs and constraints against the live network. Throws NetworkModificationException on conflict or missing prerequisites. Default implementation does nothing. |
void initApplicationContext(IFilterService filterService, ILoadFlowService loadFlowService) |
Injects external service instances. Called prior to check when service dependencies exist. Default implementation does nothing. |
void apply(Network network, ReportNode subReportNode) |
Mutates the Network and logs structured progress and audit messages to subReportNode. |
void apply(Network network, NamingStrategy namingStrategy, ReportNode subReportNode) |
Variant supporting a custom naming strategy. Defaults to delegating to apply(network, subReportNode). |
String getName() |
Returns the descriptive name for the modification type. |
Package: org.gridsuite.modification.dto
JSON Discriminator Property: type (matches ModificationType enum name)
| Field | Type | Description |
|---|---|---|
uuid |
UUID |
Unique identifier of this modification instance |
type |
ModificationType |
Discriminator property; automatically derived from @JsonTypeName on concrete subclasses |
date |
Instant |
Creation or update timestamp |
stashed |
Boolean |
Staging flag (default false). When true, skipped during execution |
activated |
Boolean |
Activation flag (default true). When false, skipped during execution |
description |
String |
Optional free-text description |
messageType |
String |
i18n message template key |
messageValues |
String |
Serialized message interpolation parameters |
| Method | Description |
|---|---|
AbstractModification toModification() |
Factory method instantiating the corresponding AbstractModification. |
ReportNode createSubReportNode(ReportNode reportNode) |
Creates and attaches a child ReportNode with the appropriate message template. |
void check() |
Validates internal DTO fields before conversion. |
ModificationType getType() |
Returns the modification type enum value. |
Map<String, String> getMapMessageValues() |
Returns message interpolation values as key-value pairs. |
Package: org.gridsuite.modification
Supported modification types in ModificationType.java:
| Modification Type | Category |
|---|---|
LOAD_CREATION |
Injections |
LOAD_MODIFICATION |
Injections |
BATTERY_CREATION |
Injections |
BATTERY_MODIFICATION |
Injections |
GENERATOR_CREATION |
Injections |
GENERATOR_MODIFICATION |
Injections |
SHUNT_COMPENSATOR_CREATION |
Injections |
SHUNT_COMPENSATOR_MODIFICATION |
Injections |
STATIC_VAR_COMPENSATOR_CREATION |
Injections |
LINE_CREATION |
Branches |
LINE_MODIFICATION |
Branches |
TWO_WINDINGS_TRANSFORMER_CREATION |
Branches |
TWO_WINDINGS_TRANSFORMER_MODIFICATION |
Branches |
SUBSTATION_CREATION |
Substations & Voltage Levels |
SUBSTATION_MODIFICATION |
Substations & Voltage Levels |
VOLTAGE_LEVEL_CREATION |
Substations & Voltage Levels |
VOLTAGE_LEVEL_MODIFICATION |
Substations & Voltage Levels |
VSC_CREATION |
HVDC |
VSC_MODIFICATION |
HVDC |
CONVERTER_STATION_CREATION |
HVDC |
CONVERTER_STATION_MODIFICATION |
HVDC |
LCC_CREATION |
HVDC |
LCC_MODIFICATION |
HVDC |
LCC_CONVERTER_STATION_CREATION |
HVDC |
LCC_CONVERTER_STATION_MODIFICATION |
HVDC |
EQUIPMENT_DELETION |
Deletion |
BY_FILTER_DELETION |
Deletion |
LINE_SPLIT_WITH_VOLTAGE_LEVEL |
Topology |
LINE_ATTACH_TO_VOLTAGE_LEVEL |
Topology |
LINES_ATTACH_TO_SPLIT_LINES |
Topology |
DELETE_VOLTAGE_LEVEL_ON_LINE |
Topology |
DELETE_ATTACHING_LINE |
Topology |
VOLTAGE_LEVEL_TOPOLOGY_MODIFICATION |
Topology |
CREATE_COUPLING_DEVICE |
Topology |
CREATE_VOLTAGE_LEVEL_TOPOLOGY |
Topology |
CREATE_VOLTAGE_LEVEL_SECTION |
Topology |
MOVE_VOLTAGE_LEVEL_FEEDER_BAYS |
Topology |
GENERATOR_SCALING |
Scaling & Dispatch |
LOAD_SCALING |
Scaling & Dispatch |
GENERATION_DISPATCH |
Scaling & Dispatch |
BALANCES_ADJUSTMENT_MODIFICATION |
Operational |
OPERATING_STATUS_MODIFICATION |
Operational |
VOLTAGE_INIT_MODIFICATION |
Operational |
EQUIPMENT_ATTRIBUTE_MODIFICATION |
Bulk & Programmatic |
GROOVY_SCRIPT |
Bulk & Programmatic |
TABULAR_MODIFICATION |
Bulk & Programmatic |
TABULAR_CREATION |
Bulk & Programmatic |
LIMIT_SETS_TABULAR_MODIFICATION |
Bulk & Programmatic |
BY_FORMULA_MODIFICATION |
Bulk & Programmatic |
MODIFICATION_BY_ASSIGNMENT |
Bulk & Programmatic |
COMPOSITE_MODIFICATION |
Composition & Reference |
MODIFICATION_REFERENCE |
Composition & Reference |
Base class for modifications targeting an existing equipment entity.
| Field | Type | Description |
|---|---|---|
equipmentId |
String |
Required. Identifier of the target equipment |
properties |
List<FreePropertyInfos> |
Custom key-value properties to assign or delete |
Lightweight DTO for simple equipment property alterations.
| Field | Type | Description |
|---|---|---|
equipmentName |
String |
Human-readable name for the new equipment |
Base class for injection equipment creations.
| Field | Type | Description |
|---|---|---|
voltageLevelId |
String |
Required. Voltage level identifier |
busOrBusbarSectionId |
String |
Required. Bus (bus-breaker) or busbar section (node-breaker) identifier |
connectionName |
String |
Feeder connection name |
connectionDirection |
ConnectablePosition.Direction |
Direction: TOP, BOTTOM, or UNDEFINED |
connectionPosition |
Integer |
Feeder position index in the bay |
terminalConnected |
Boolean |
Initial connection status (default true) |
Base class for branch equipment creations (lines, transformers).
| Field | Type | Description |
|---|---|---|
voltageLevelId1 / voltageLevelId2 |
String |
Voltage level ID at terminals 1 & 2 |
busOrBusbarSectionId1 / Id2 |
String |
Bus/busbar section ID at terminals 1 & 2 |
connectionName1 / Name2 |
String |
Connection name at terminals 1 & 2 |
connectionDirection1 / Direction2 |
ConnectablePosition.Direction |
Connection direction at terminals 1 & 2 |
connectionPosition1 / Position2 |
Integer |
Feeder position order at terminals 1 & 2 |
connected1 / connected2 |
Boolean |
Connection status at terminals 1 & 2 |
currentLimits1 / currentLimits2 |
CurrentLimitsInfos |
Permanent and temporary current limits at terminals 1 & 2 |
| Field | Type | Description |
|---|---|---|
loadType |
LoadType |
UNDEFINED, AUXILIARY, FICTITIOUS |
p0 |
double |
Active power consumption (MW) |
q0 |
double |
Reactive power consumption (MVar) |
| Field | Type | Description |
|---|---|---|
energySource |
EnergySource |
HYDRO, NUCLEAR, WIND, SOLAR, THERMAL, OTHER, … |
minP / maxP |
double |
Minimum / maximum active power output (MW) |
ratedS |
Double |
Rated nominal apparent power (MVA) |
targetP |
double |
Active power set point (MW) |
targetQ |
Double |
Reactive power set point (MVar) |
voltageRegulationOn |
boolean |
Voltage regulation enabled |
targetV |
Double |
Voltage set point (kV) |
minQ / maxQ |
Double |
Minimum / maximum reactive power limits (MVar) |
plannedActivePowerSetPoint |
Double |
Planned active power set point |
marginalCost |
Double |
Marginal generation cost |
plannedOutageRate / forcedOutageRate |
Double |
Outage rates |
reactiveCapabilityCurvePoints |
List<ReactiveCapabilityCurvePointsInfos> |
Reactive capability curve definition |
regulatingTerminalId |
String |
Remote terminal ID for regulation |
regulatingTerminalType |
String |
Remote terminal equipment type |
regulatingTerminalVlId |
String |
Remote terminal voltage level ID |
qPercent |
Double |
Reactive droop coefficient |
stepUpTransformerX |
Double |
Step-up transformer reactance (Ω) |
directTransX |
Double |
Direct-axis transient reactance |
participate |
Boolean |
Participation in frequency control |
droop |
Float |
Frequency droop coefficient |
| Field | Type | Description |
|---|---|---|
minP / maxP |
double |
Active power limits (MW) |
targetP / targetQ |
double / Double |
Active / reactive power set points |
participate |
Boolean |
Frequency control participation |
droop |
Float |
Frequency droop coefficient |
minQ / maxQ |
Double |
Reactive power limits |
reactiveCapabilityCurvePoints |
List<ReactiveCapabilityCurvePointsInfos> |
Reactive capability curve points |
| Field | Type | Description |
|---|---|---|
maxSusceptance |
Double |
Maximum susceptance (S) |
maxQAtNominalV |
Double |
Maximum reactive power at nominal voltage (MVar) |
shuntCompensatorType |
ShuntCompensatorType |
CAPACITOR or REACTOR |
sectionCount / maximumSectionCount |
Integer |
Current and maximum section count |
regulatingTerminalId / Type / VlId |
String |
Regulating terminal descriptor |
voltageSetpoint |
Double |
Voltage set point (kV) |
qPercent |
Double |
Reactive droop percentage |
| Field | Type | Description |
|---|---|---|
minSusceptance / maxSusceptance |
Double |
Susceptance boundaries (S) |
minQ / maxQ |
Double |
Reactive power boundaries (MVar) |
regulationMode |
StaticVarCompensator.RegulationMode |
VOLTAGE, REACTIVE_POWER, OFF |
voltageSetpoint |
Double |
Target voltage set point (kV) |
reactivePowerSetpoint |
Double |
Target reactive power set point (MVar) |
voltageRegulationType |
VoltageRegulationType |
LOCAL or DISTANT |
regulatingTerminalId / Type / VlId |
String |
Remote regulation terminal properties |
| Field | Type | Description |
|---|---|---|
r |
double |
Series resistance (Ω) |
x |
double |
Series reactance (Ω) |
g1 / b1 |
double |
Shunt conductance / susceptance at terminal 1 (S) |
g2 / b2 |
double |
Shunt conductance / susceptance at terminal 2 (S) |
| Field | Type | Description |
|---|---|---|
r |
double |
Series resistance (Ω) |
x |
double |
Series reactance (Ω) |
g / b |
double |
Magnetizing conductance / susceptance (S) |
ratedU1 / ratedU2 |
double |
Rated voltages at terminals 1 & 2 (kV) |
ratedS |
Double |
Rated nominal apparent power (MVA) |
ratioTapChanger |
RatioTapChangerCreationInfos |
Optional ratio tap changer configuration |
phaseTapChanger |
PhaseTapChangerCreationInfos |
Optional phase tap changer configuration |
Injection modification DTOs utilize AttributeModification<T> properties for selective, partial updates.
| Field | Type | Description |
|---|---|---|
voltageLevelId |
AttributeModification<String> |
Target voltage level |
busOrBusbarSectionId |
AttributeModification<String> |
Target bus / busbar section |
| Field | Type | Description |
|---|---|---|
loadType |
AttributeModification<LoadType> |
Load type |
p0 |
AttributeModification<Double> |
Active power consumption (MW) |
q0 |
AttributeModification<Double> |
Reactive power consumption (MVar) |
| Field | Type | Description |
|---|---|---|
energySource |
AttributeModification<EnergySource> |
Energy source |
minP / maxP |
AttributeModification<Double> |
Active power boundaries (MW) |
ratedS |
AttributeModification<Double> |
Rated apparent power (MVA) |
targetP / targetQ / targetV |
AttributeModification<Double> |
Operational set points |
voltageRegulationOn |
AttributeModification<Boolean> |
Voltage regulation status |
participate |
AttributeModification<Boolean> |
Frequency regulation participation |
droop |
AttributeModification<Float> |
Droop coefficient |
reactiveCapabilityCurvePoints |
List<ReactiveCapabilityCurvePointsInfos> |
Capability curve points |
Mirrors generator modification attributes applicable to battery storage systems.
| Field | Type | Description |
|---|---|---|
sectionCount |
AttributeModification<Integer> |
Number of active sections |
maximumSectionCount |
AttributeModification<Integer> |
Maximum section capacity |
voltageSetpoint |
AttributeModification<Double> |
Target voltage set point |
| Field | Type | Description |
|---|---|---|
r / x |
AttributeModification<Double> |
Resistance / Reactance |
operationalLimitsGroups1 / 2 |
List<OperationalLimitsGroupModificationInfos> |
Limit group modifications at terminals 1 & 2 |
connected1 / connected2 |
AttributeModification<Boolean> |
Terminal connection status |
Adds g1, b1, g2, b2 wrapped in AttributeModification<Double>.
Adds g, b, ratedU1, ratedU2, ratedS, ratioTapChanger, and phaseTapChanger attribute modifications.
| Field | Type | Description |
|---|---|---|
country |
Country |
Country code (ISO 3166-1 alpha-2) |
voltageLevels |
List<VoltageLevelCreationInfos> |
Child voltage levels to instantiate within substation |
| Field | Type | Description |
|---|---|---|
country |
AttributeModification<Country> |
Updated country code |
| Field | Type | Description |
|---|---|---|
substationId |
String |
Parent substation identifier |
nominalV |
double |
Nominal voltage (kV) |
lowVoltageLimit / highVoltageLimit |
Double |
Operating voltage limits (kV) |
ipMin / ipMax |
Double |
Short-circuit current limits (A) |
busbarCount |
int |
Number of busbars (node-breaker) |
sectionCount |
int |
Section count per busbar |
switchKinds |
List<SwitchKind> |
Switch types between sections |
couplingDevices |
List<CouplingDeviceInfos> |
Initial coupling devices |
topologyKind |
TopologyKind |
BUS_BREAKER or NODE_BREAKER |
| Field | Type | Description |
|---|---|---|
nominalV |
AttributeModification<Double> |
Nominal voltage |
lowVoltageLimit / highVoltageLimit |
AttributeModification<Double> |
Voltage operating limits |
ipMin / ipMax |
AttributeModification<Double> |
Current limits |
| Field | Type | Description |
|---|---|---|
dcNominalVoltage |
double |
DC nominal voltage (kV) |
dcResistance |
double |
DC line resistance (Ω) |
nominalV |
double |
AC nominal voltage (kV) |
maxP |
double |
Maximum active power capacity (MW) |
activePowerSetpoint |
double |
Active power set point (MW) |
operatorActivePowerLimitSide1 / Side2 |
Float |
Operator limits |
convertersMode |
HvdcLine.ConvertersMode |
Converter rectifier/inverter modes |
converterStation1 / converterStation2 |
ConverterStationCreationInfos |
VSC converter station specifications |
angleDroopActivePowerControl |
Boolean |
Enable angle droop control |
p0 / droop |
Float |
Active power reference and droop slope |
| Field | Type | Description |
|---|---|---|
nominalV / dcNominalVoltage / dcResistance |
double |
Electrical parameters |
maxP / activePowerSetpoint |
double |
Power limits and set points |
convertersMode |
HvdcLine.ConvertersMode |
Converter mode |
converterStation1 / converterStation2 |
LccConverterStationCreationInfos |
LCC converter stations |
| DTO Class | Fields | Purpose |
|---|---|---|
LineSplitWithVoltageLevelInfos |
lineToSplitId, percent, mayNewVoltageLevelInfos, existingVoltageLevelId, bbsOrBusId, newLine1Id, newLine2Id, newLine1Name, newLine2Name |
Split line by inserting a voltage level |
LineAttachToVoltageLevelInfos |
lineToAttachToId, percent, attachmentPointId, attachmentPointName, mayNewVoltageLevelInfos, existingVoltageLevelId, bbsOrBusId, attachmentLineId, attachmentLineName, newLine1Id, newLine2Id |
Attach end of line to a voltage level |
LinesAttachToSplitLinesInfos |
lineToAttachTo1Id, lineToAttachTo2Id, attachedLineId, voltageLevelId, bbsBusId, replacingLine1Id, replacingLine1Name, replacingLine2Id, replacingLine2Name |
Attach lines around a split configuration |
DeleteVoltageLevelOnLineInfos |
lineToAttachTo1Id, lineToAttachTo2Id, replacingLine1Id, replacingLine1Name |
Remove intermediate voltage level from line |
DeleteAttachingLineInfos |
lineToAttachTo1Id, lineToAttachTo2Id, attachedLineId, replacingLine1Id, replacingLine1Name |
Delete attaching line |
CreateCouplingDeviceInfos |
voltageLevelId, couplingDeviceInfos |
Add coupling breaker between busbars |
CreateVoltageLevelTopologyInfos |
substationId, voltageLevelId, voltageLevelName, nominalV, lowVoltageLimit, highVoltageLimit, busbarCount, sectionCount, switchKinds |
Create full voltage level topology |
CreateVoltageLevelSectionInfos |
voltageLevelId, switchKinds |
Add a section to an existing voltage level |
MoveVoltageLevelFeederBaysInfos |
voltageLevelId, feederBaysMoves |
Reallocate bays across busbar sections |
VoltageLevelTopologyModificationInfos |
busbarSectionToSwitchesAttributes |
Update switch topology configuration |
Deletes a single piece of equipment identified by equipmentId and equipmentType.
Deletes all equipment matching filter criteria.
| Field | Type | Description |
|---|---|---|
equipmentType |
IdentifiableType |
Target equipment type |
filters |
List<FilterInfos> |
Filter identifiers used to select equipment |
Abstract base for power scaling.
| Field | Type | Description |
|---|---|---|
variations |
List<ScalingVariationInfos> |
List of scaling variations |
variationType |
VariationType |
DELTA_P (relative delta) or TARGET_P (absolute value) |
GeneratorScalingInfos←ScalingInfos(scales active power across selected generators).LoadScalingInfos←ScalingInfos(scales active power across selected loads).
| Field | Type | Description |
|---|---|---|
filters |
List<FilterInfos> |
Selection filter definitions |
variationMode |
VariationMode |
PROPORTIONAL_TO_PMAX, PROPORTIONAL_TO_P, REGULAR_DISTRIBUTION, STACKING_UP, VENTILATION |
variationValue |
double |
Target power variation value (MW) |
reactiveVariationMode |
ReactiveVariationMode |
CONSTANT_Q or TAN_PHI_FIXED |
| Field | Type | Description |
|---|---|---|
lossCoefficient |
double |
Loss percentage factor |
defaultOutageRate |
double |
Generator outage rate default |
generatorsWithoutOutage |
List<GeneratorsWithoutOutageInfos> |
Exempted generators |
generatorsWithFixedSupply |
List<GeneratorsFilterInfos> |
Fixed supply generators |
generatorsFrequencyReserve |
List<GeneratorsFrequencyReserveInfos> |
Frequency reserve allocation |
substationsGeneratorsOrdering |
List<SubstationsGeneratorsOrderingInfos> |
Dispatch ordering preferences |
loadFlowParametersUuid |
UUID |
Load-flow settings reference |
| DTO Class | Fields | Purpose |
|---|---|---|
EquipmentAttributeModificationInfos |
equipmentAttributeName, equipmentAttributeValue, equipmentType |
Modify a specific attribute by name |
GroovyScriptInfos |
script |
Execute dynamic Groovy script on network |
TabularModificationInfos |
modificationType, modifications |
Batch modify multiple equipment from a table |
TabularCreationInfos |
creationType, creations |
Batch create multiple equipment from a table |
LimitSetsTabularModificationInfos |
Inherits TabularModificationInfos |
Bulk edit operational limit sets |
ByFormulaModificationInfos |
identifiableType, formulaInfosList |
Calculate attribute values via mathematical expressions |
ModificationByAssignmentInfos |
identifiableType, assignmentInfosList |
Assign values based on filter conditions |
| Field | Type | Description |
|---|---|---|
energizedVoltageLevelId |
String |
Voltage level providing energization |
action |
ActionType |
LOCKOUT, TRIP, SWITCH_ON, ENERGISE_END_ONE, ENERGISE_END_TWO |
| Field | Type | Description |
|---|---|---|
areas |
List<BalancesAdjustmentAreaInfos> |
Area exchange targets |
loadFlowParametersUuid |
UUID |
Load-flow settings reference |
Contains collections of voltage initialization targets for generators, transformers, staticVarCompensators, vscConverterStations, shuntCompensators, and buses.
| Field | Type | Description |
|---|---|---|
name |
String |
Descriptive scenario/composite name |
modificationsInfos |
List<ModificationInfos> |
Ordered list of child modifications |
maxDepth |
Integer |
Computed maximum nesting depth |
| Field | Type | Description |
|---|---|---|
referencedId |
UUID |
UUID of the referenced modification |
referenceType |
Type |
BASIC or DIRECTORY |
referencedInfos |
ModificationInfos |
Resolved DTO representation |
Generic container for partial update operations:
// Explicit update
AttributeModification<Double> setP = new AttributeModification<>(250.0, OperationType.SET);
// Reset to default
AttributeModification<Double> unsetP = new AttributeModification<>(null, OperationType.UNSET);
// Helper factory
AttributeModification<Double> modP = AttributeModification.toAttributeModification(250.0, OperationType.SET);Carries UUID id and String name for referencing filter rules.
Carries Double permanentLimit and List<CurrentTemporaryLimitCreationInfos> temporaryLimits.
Carries String name, String value, and boolean deletionMark for arbitrary equipment metadata tags.
Package: org.gridsuite.modification.error
NetworkModificationException extends com.powsybl.commons.PowsyblException and encapsulates domain-level errors encountered during check or apply phases.
| Type | Default Message |
|---|---|
GROOVY_SCRIPT_EMPTY |
The groovy script is empty |
LINE_NOT_FOUND |
The line could not be found |
LOAD_NOT_FOUND |
The load could not be found |
BATTERY_NOT_FOUND |
The battery could not be found |
GENERATOR_NOT_FOUND |
The generator could not be found |
TWO_WINDINGS_TRANSFORMER_NOT_FOUND |
The two windings transformer could not be found |
UNKNOWN_EQUIPMENT_TYPE |
The equipment type is unknown |
WRONG_EQUIPMENT_TYPE |
The equipment type does not match the expected type |
MODIFICATION_ERROR |
An error occurred while applying the modification |
VOLTAGE_LEVEL_NOT_FOUND |
The voltage level could not be found |
BUSBAR_SECTION_NOT_FOUND |
The busbar section could not be found |
BUS_NOT_FOUND |
The bus could not be found |
CREATE_BATTERY_ERROR |
An error occurred while creating the battery |
CREATE_GENERATOR_ERROR |
An error occurred while creating the generator |
CREATE_SHUNT_COMPENSATOR_ERROR |
An error occurred while creating the shunt compensator |
MODIFY_SHUNT_COMPENSATOR_ERROR |
An error occurred while modifying the shunt compensator |
CREATE_STATIC_VAR_COMPENSATOR_ERROR |
An error occurred while creating the static var compensator |
EQUIPMENT_NOT_FOUND |
The equipment could not be found |
ATTRIBUTE_NOT_EDITABLE |
The equipment attribute is not editable |
CREATE_LINE_ERROR |
An error occurred while creating the line |
MODIFY_LINE_ERROR |
An error occurred while modifying the line |
CREATE_TWO_WINDINGS_TRANSFORMER_ERROR |
An error occurred while creating the two windings transformer |
MODIFY_TWO_WINDINGS_TRANSFORMER_ERROR |
An error occurred while modifying the two windings transformer |
CREATE_VOLTAGE_LEVEL_ERROR |
An error occurred while creating the voltage level |
MODIFY_VOLTAGE_LEVEL_ERROR |
An error occurred while modifying the voltage level |
SUBSTATION_NOT_FOUND |
The substation could not be found |
BATTERY_ALREADY_EXISTS |
A battery with this identifier already exists |
LOAD_ALREADY_EXISTS |
A load with this identifier already exists |
VOLTAGE_LEVEL_ALREADY_EXISTS |
A voltage level with this identifier already exists |
GENERATOR_ALREADY_EXISTS |
A generator with this identifier already exists |
SHUNT_COMPENSATOR_ALREADY_EXISTS |
A shunt compensator with this identifier already exists |
SHUNT_COMPENSATOR_NOT_FOUND |
The shunt compensator could not be found |
STATIC_VAR_COMPENSATOR_ALREADY_EXISTS |
A static var compensator with this identifier already exists |
STATIC_VAR_COMPENSATOR_NOT_FOUND |
The static var compensator could not be found |
LINE_ALREADY_EXISTS |
A line with this identifier already exists |
TWO_WINDINGS_TRANSFORMER_ALREADY_EXISTS |
A two windings transformer with this identifier already exists |
TWO_WINDINGS_TRANSFORMER_CREATION_ERROR |
An error occurred while creating the two windings transformer |
BRANCH_MODIFICATION_ERROR |
An error occurred while modifying the branch |
INJECTION_MODIFICATION_ERROR |
An error occurred while modifying the injection |
MODIFY_BATTERY_ERROR |
An error occurred while modifying the battery |
OPERATING_STATUS_MODIFICATION_ERROR |
An error occurred while modifying the operating status |
OPERATING_ACTION_TYPE_EMPTY |
The operating action type is empty |
OPERATING_ACTION_TYPE_UNSUPPORTED |
The operating action type is not supported |
EQUIPMENT_TYPE_UNSUPPORTED |
The equipment type is not supported |
MODIFY_GENERATOR_ERROR |
An error occurred while modifying the generator |
EQUIPMENT_ATTRIBUTE_NAME_ERROR |
The equipment attribute name is invalid |
EQUIPMENT_ATTRIBUTE_VALUE_ERROR |
The equipment attribute value is invalid |
GENERATOR_SCALING_ERROR |
An error occurred while scaling the generators |
LOAD_SCALING_ERROR |
An error occurred while scaling the loads |
GENERATION_DISPATCH_ERROR |
An error occurred while dispatching the generation |
VOLTAGE_INIT_MODIFICATION_ERROR |
An error occurred while applying the voltage init modification |
TABULAR_MODIFICATION_ERROR |
An error occurred while applying the tabular modification |
TABULAR_CREATION_ERROR |
An error occurred while applying the tabular creation |
CREATE_VSC_ERROR |
An error occurred while creating the VSC converter station |
MODIFY_VSC_ERROR |
An error occurred while modifying the VSC converter station |
CREATE_LCC_ERROR |
An error occurred while creating the LCC converter station |
MODIFY_LCC_ERROR |
An error occurred while modifying the LCC converter station |
HVDC_LINE_ALREADY_EXISTS |
An HVDC line with this identifier already exists |
VSC_CONVERTER_STATION_NOT_FOUND |
The VSC converter station could not be found |
LCC_CONVERTER_STATION_NOT_FOUND |
The LCC converter station could not be found |
BY_FORMULA_MODIFICATION_ERROR |
An error occurred while applying the modification by formula |
MODIFICATION_BY_ASSIGNMENT_ERROR |
An error occurred while applying the modification by assignment |
HVDC_LINE_NOT_FOUND |
The HVDC line could not be found |
WRONG_HVDC_ANGLE_DROOP_ACTIVE_POWER_CONTROL |
The HVDC angle droop active power control configuration is invalid |
UNSUPPORTED_HYBRID_HVDC |
The hybrid HVDC line is not supported |
MODIFY_VOLTAGE_LEVEL_TOPOLOGY_ERROR |
An error occurred while modifying the voltage level topology |
CREATE_VOLTAGE_LEVEL_TOPOLOGY_ERROR |
An error occurred while creating the voltage level topology |
MOVE_VOLTAGE_LEVEL_FEEDER_BAYS_ERROR |
An error occurred while moving the voltage level feeder bays |
SET (apply new value), UNSET (reset to default/null).
DELTA_P (relative change), TARGET_P (absolute value).
PROPORTIONAL_TO_PMAX, PROPORTIONAL_TO_P, REGULAR_DISTRIBUTION, STACKING_UP, VENTILATION.
CONSTANT_Q (keep Q constant), TAN_PHI_FIXED (keep power factor fixed).
RATIO, PHASE.
CAPACITOR, REACTOR.
LOCAL, DISTANT.
SIDE_1, SIDE_2.
LOCKOUT, TRIP, SWITCH_ON, ENERGISE_END_ONE, ENERGISE_END_TWO.
LoadCreationInfos loadInfos = LoadCreationInfos.builder()
.equipmentId("LOAD_1")
.equipmentName("Industrial Load 1")
.voltageLevelId("VL_NORTH_400")
.busOrBusbarSectionId("BUS_1")
.loadType(LoadType.UNDEFINED)
.p0(120.0)
.q0(30.0)
.build();
loadInfos.check();
AbstractModification modification = loadInfos.toModification();
modification.check(network);
ReportNode reportNode = ReportNode.newRootReportNode()
.withMessageTemplate("root", "Root Report")
.build();
modification.apply(network, reportNode);GeneratorModificationInfos genModif = GeneratorModificationInfos.builder()
.equipmentId("GEN_HYDRO_1")
.targetP(AttributeModification.toAttributeModification(280.0, OperationType.SET))
.voltageRegulationOn(AttributeModification.toAttributeModification(true, OperationType.SET))
.build();
genModif.toModification().apply(network, reportNode);ByFilterDeletionInfos deletion = ByFilterDeletionInfos.builder()
.equipmentType(IdentifiableType.LOAD)
.filters(List.of(new FilterInfos(filterUuid, "Decommissioned Loads")))
.build();
AbstractModification mod = deletion.toModification();
mod.initApplicationContext(filterService, null);
mod.check(network);
mod.apply(network, reportNode);CompositeModificationInfos scenario = CompositeModificationInfos.builder()
.name("Peak Load Scenario")
.modificationsInfos(List.of(loadInfos, genModif))
.build();
AbstractModification compositeMod = scenario.toModification();
compositeMod.initApplicationContext(filterService, loadFlowService);
compositeMod.check(network);
compositeMod.apply(network, reportNode);[
{
"type": "LOAD_CREATION",
"equipmentId": "LOAD_NEW",
"voltageLevelId": "VL1",
"busOrBusbarSectionId": "BUS1",
"p0": 45.0,
"q0": 12.0
},
{
"type": "GENERATOR_MODIFICATION",
"equipmentId": "GEN1",
"targetP": {
"value": 310.0,
"op": "SET"
}
}
]ObjectMapper mapper = new ObjectMapper();
List<ModificationInfos> modifications = mapper.readValue(
jsonString,
mapper.getTypeFactory().constructCollectionType(List.class, ModificationInfos.class)
);Documentation for gridsuite-network-modification — © RTE (http://www.rte-france.com) — MPL-2.0