107 changes: 106 additions & 1 deletion NEWS.adoc
Original file line number Diff line number Diff line change
Expand Up @@ -511,7 +511,112 @@ https://github.com/networkupstools/nut/milestone/13
some problems possible when iterating devices. [issue #1768, PR #3477]

- `riello_usb`, `riello_ser` driver updates:
* riello_usb, riello_ser: report NAK on RE as failure [issue #3546]
* riello_usb, riello_ser: report NAK on RE as failure. [issue #3546]

- `tripplitesu` driver updates [PR #3273]:
* The bypass (transfer) reason recorded by the device is now published
as the read-only `input.transfer.reason` variable, refreshed on every
poll, and the existing `clear.fault.record` instant command clears
the recorded reason on the device.
* Device settings (`outlet.delay.start`, `ups.start.auto`,
`ups.watchdog.status`, `input.eco.switchable` and
`ups.beeper.status`) are no longer published with assumed values when
the device does not report them: they appear, and become settable,
only once the device has reported them. A setting that was read
before keeps its last known value when the device stops answering,
and a warning is logged instead of silently falling back to a
default.
* Added the `offdelay` and `startdelay` settings in `ups.conf` (in
seconds and whole minutes respectively, the units of the two device
commands). The `shutdown.return` and `shutdown.stayoff` instant
commands accept an optional shutdown delay in seconds, while
`shutdown.reboot` and `shutdown.reboot.graceful` accept
`off[:on]` - a mandatory shutdown delay in seconds and an optional
restart delay in minutes - so that the timers can be chosen per
invocation without restarting the driver or changing its
configuration. Invalid values are rejected before anything is sent.
* Added control of the individual outlet banks through the
`outlet.n.load.off` and `outlet.n.load.on` instant commands, and the
matching `outlet.count`, `outlet.n.status` and `outlet.n.switchable`
variables.
* Added the `shutdown.stayoff` instant command, and made the
shutdown-related commands keep the device return delay consistent with
what they mean: the two reboot commands set it to the requested
restart delay, while `shutdown.return` and `shutdown.stayoff` clear it,
so that the load comes back only when mains is (re)applied, or not at
all. The driver no longer adjusts the return delay against the
shutdown delay or rounds it: both are sent in the units the device
uses and the firmware decides how they interact.
* Added the read/write variables `ups.beeper.status`, `ups.start.auto`,
`ups.watchdog.status`, `outlet.delay.start` and
`input.eco.switchable`, the `battery.date` variable, the `beeper.mute`
and `clear.fault.record` instant commands, and validation of
`input.transfer.low`/`.high` against the ranges reported by the device
(published as `input.transfer.low.min`/`.max` and
`input.transfer.high.min`/`.max`).
* Instant commands and variable writes now report a failure when the
device rejects or does not answer one of the operations they perform,
instead of always reporting success.
* Added the `command_delay` setting in `ups.conf` as a minimum interval
between two commands sent to the UPS, in milliseconds, to work around
units that do not answer a command sent too soon after the previous
one. The interval is measured from the previous command, so an idle
link is not penalized, and the configured value is used unchanged:
there is no automatic adjustment after a timeout. The former `-1`
automatic mode is no longer accepted; use `0` or an explicit interval.
* The watchdog is disarmed when the driver exits on purpose (a handled
signal, the `driver.exit` instant command or the end of a data dump),
so that a driver restart - for example during a package upgrade - does
not leave an armed watchdog that would power cycle the load. A
watchdog the driver never saw enabled, or one already disabled, is left
untouched, and a crash or a SIGKILL does not disarm it.
* Added the read/write `ups.watchdog.timeout` and `ups.watchdog.alarm`
variables, which expose the two fields the device stores for its
watchdog - the timeout in seconds, 0 disabling the watchdog, and the
restart-alarm flag - instead of only the derived
`ups.watchdog.status`, and the `reset.watchdog` instant command, which
sends the watchdog setting the driver has again to restart its timer.
The watchdog is disabled by default, has to be armed explicitly, and
returns to disabled after it trips; `reset.watchdog` now fails when the
timeout is 0 instead of reporting a successful kick of a watchdog that
is not running.
* The device restarts its watchdog timer on any command it receives, not
only on a kick, so the driver's own polls usually keep an armed watchdog
quiet as well. The documentation still tells the user to kick it
explicitly with `reset.watchdog`, because the polling cadence is an
implementation detail (`pollinterval` can be longer than the watchdog
timeout) and not a guarantee.
* The watchdog setting is re-read on every update cycle while the watchdog
is armed, so a watchdog that trips, power cycles the load and comes back
disabled shows up as `ups.watchdog.status` = `disabled`, with the
timeout and restart-alarm flag that come with it, even when the driver
keeps running across the restart, for example on a machine that is not
powered by the UPS.
* The driver shutdown handling (`shutdown.default`, which
`upsdrvctl shutdown` runs) always asks the device to start the load
again when mains is (re)applied (the auto-reboot setting is turned on),
so that every outlet is powered again after the outage, and the new
`shutdown_mode` setting decides whether it stops at the first operation
the device rejects or does not answer (`abort`, fail safe) or keeps
sending the rest (`continue`, best effort, the default).
It also clears the return delay (0 minutes), so that the load does not
come back on a timer left over from an earlier command, and schedules
the shutdown after `offdelay`.
* The multi-frame commands (`load.off` and `load.on`, which walk the
outlet banks) stop at the first frame the device rejects or does not
answer, as the shutdown commands already did, instead of sending the
remaining frames.
* Hardened protocol handling: requests are length-checked against the
protocol and buffer limits, replies must arrive complete and exactly
as announced, and semicolon-separated fields are copied with a bound
instead of being used in place.
* Added the `ups.start` instant command, which starts the load of a
device that is off: it turns the auto-reboot setting on and writes the
restart delay, which is what makes the device start its outputs. The
delay is passed as the command value, in minutes, and defaults to the
`startdelay` setting (`ups.start 0` starts as soon as the device can);
a device that is already running is not switched off, it only gets the
delay stored.

- `usbhid-ups` driver updates:
* When reconnecting, report success more visibly (not only in debug), and
Expand Down
5 changes: 5 additions & 0 deletions data/cmdvartab
Original file line number Diff line number Diff line change
Expand Up @@ -43,6 +43,9 @@ VARDESC ups.start.auto "UPS starts when mains is (re)applied"
VARDESC ups.start.battery "Allow to start UPS from battery"
VARDESC ups.start.reboot "UPS reboots when power returns during shutdown delay"
VARDESC ups.shutdown "Enable or disable UPS shutdown ability (poweroff)"
VARDESC ups.watchdog.status "UPS watchdog status (enabled or disabled)"
VARDESC ups.watchdog.timeout "UPS watchdog timeout (seconds, 0 disables)"
VARDESC ups.watchdog.alarm "UPS watchdog restart alarm (enabled or disabled)"

VARDESC input.voltage "Input voltage (V)"
VARDESC input.voltage.extended "Extended input voltage range"
Expand Down Expand Up @@ -168,6 +171,7 @@ VARDESC ambient.contacts.2.status "State of the dry contact sensor 2"
#
# VARDESC outlet.[[:digit:]]+.id "Outlet system identifier (<index>)"

VARDESC outlet.count "Total number of outlets"
VARDESC outlet.id "Outlet system identifier"
VARDESC outlet.desc "Outlet description"
VARDESC outlet.switch "Outlet switch control"
Expand Down Expand Up @@ -240,6 +244,7 @@ CMDDESC driver.reload-or-exit "Reload running driver configuration from the file
CMDDESC load.off "Turn off the load immediately"
CMDDESC load.on "Turn on the load immediately"
CMDDESC load.cycle "Power-cycle the load (off then back on)"
CMDDESC ups.start "Start the load of a UPS that is off, possibly after a delay"
CMDDESC shutdown.default "Run the driver-defined UPS shutdown sequence (as opposed to user-configured 'sdcommands')"
CMDDESC shutdown.return "Turn off the load and return when power is back"
CMDDESC shutdown.stayoff "Turn off the load and remain off"
Expand Down